The JNIOR will publish all status information to topics starting with
jnior/[SERIAL_NUMBER]/status/...
.
The JNIOR will publish all Relay Output status information to topics in the format
jnior/[SERIAL_NUMBER]/status/digital/outputs/[CHANNEL_NUMBER]/[PROPERTY]
.
Output channel numbers can be 1 - x, depending on the model and how many external
4ROUTS are connected. The property will either be state or usagemeter.
jnior/[SERIAL_NUMBER]/status/digital/outputs/[CHANNEL_NUMBER]/state jnior/[SERIAL_NUMBER]/status/digital/outputs/[CHANNEL_NUMBER]/usagemeter
The JNIOR will publish all Digital Input status information to topics in the format
jnior/[SERIAL_NUMBER]/status/digital/inputs/[CHANNEL_NUMBER]/[PROPERTY]
.
Input channel numbers can be 1 - x
, depending on the model. The property will
either be state, usagemeter or counter.
jnior/[SERIAL_NUMBER]/status/digital/inputs/[CHANNEL_NUMBER]/state jnior/[SERIAL_NUMBER]/status/digital/inputs/[CHANNEL_NUMBER]/usagemeter jnior/[SERIAL_NUMBER]/status/digital/inputs/[CHANNEL_NUMBER]/counter
The JNIOR will publish all Four to Twenty Input status information to topics in the format
jnior/[SERIAL_NUMBER]/status/fourtwenty/inputs/[CHANNEL_NUMBER]/[PROPERTY]
.
Input channel numbers can be 1 - x
, depending on the number of modules connected,
and the property will either be raw, percentage or scaled.
jnior/[SERIAL_NUMBER]/status/fourtwenty/inputs/[CHANNEL_NUMBER]/raw jnior/[SERIAL_NUMBER]/status/fourtwenty/inputs/[CHANNEL_NUMBER]/percentage jnior/[SERIAL_NUMBER]/status/fourtwenty/inputs/[CHANNEL_NUMBER]/scaled
The JNIOR will publish all Four to Twenty Output status information to topics in the format
jnior/[SERIAL_NUMBER]/status/fourtwenty/outputs/[CHANNEL_NUMBER]/[PROPERTY]
.
Output channel numbers can be 1 - x
, depending on the number of modules connected,
and the property will either be raw or scaled.
jnior/[SERIAL_NUMBER]/status/fourtwenty/outputs/[CHANNEL_NUMBER]/raw jnior/[SERIAL_NUMBER]/status/fourtwenty/outputs/[CHANNEL_NUMBER]/percentage jnior/[SERIAL_NUMBER]/status/fourtwenty/outputs/[CHANNEL_NUMBER]/scaled
The JNIOR will publish all Ten Volt Input status information to topics in the format
jnior/[SERIAL_NUMBER]/status/tenvolt/inputs/[CHANNEL_NUMBER]/[PROPERTY]
.
Input channel numbers can be 1 - x
, depending on the number of modules connected,
and the property will either be raw, percentage or scaled.
jnior/[SERIAL_NUMBER]/status/tenvolt/inputs/[CHANNEL_NUMBER]/raw jnior/[SERIAL_NUMBER]/status/tenvolt/inputs/[CHANNEL_NUMBER]/percentage jnior/[SERIAL_NUMBER]/status/tenvolt/inputs/[CHANNEL_NUMBER]/scaled
The JNIOR will publish all Ten Volt Output status information to topics in the format
jnior/[SERIAL_NUMBER]/status/tenvolt/outputs/[CHANNEL_NUMBER]/[PROPERTY]
.
Output channel numbers can be 1 - x
, depending on the number of modules connected,
and the property will either be raw or scaled.
jnior/[SERIAL_NUMBER]/status/tenvolt/outputs/[CHANNEL_NUMBER]/raw jnior/[SERIAL_NUMBER]/status/tenvolt/outputs/[CHANNEL_NUMBER]/percentage jnior/[SERIAL_NUMBER]/status/tenvolt/outputs/[CHANNEL_NUMBER]/scaled
The JNIOR will publish all Temperature Probe status information to topics in the format
jnior/[SERIAL_NUMBER]/status/tempprobe/[CHANNEL_NUMBER]/[PROPERTY]
.
Output channel numbers can be 1 - x
, depending on the number of modules connected,
and the property will either be celsius or fahrenheit.
jnior/[SERIAL_NUMBER]/status/tempprobe/[CHANNEL_NUMBER]/celsius jnior/[SERIAL_NUMBER]/status/tempprobe/[CHANNEL_NUMBER]/fahrenheit
The JNIOR will publish all Environmental Sensor status information to topics in the format
jnior/[SERIAL_NUMBER]/status/environ/[CHANNEL_NUMBER]/[PROPERTY]
.
Output channel numbers can be 1 - x
, depending on the number of modules connected,
and the property will either be celsius, fahrenheit or humidity.
jnior/[SERIAL_NUMBER]/status/environ/[CHANNEL_NUMBER]/celsius jnior/[SERIAL_NUMBER]/status/environ/[CHANNEL_NUMBER]/fahrenheit jnior/[SERIAL_NUMBER]/status/environ/[CHANNEL_NUMBER]/humidity
The JNIOR will subscribe to set commands. Those topics must start with
jnior/[SERIAL_NUMBER or HOSTNAME or DEVICE_GROUP_NAME]/set/...
.
You can command the JNIOR Relay Outputs by publishing to the following topic
jnior/[SERIAL_NUMBER or HOSTNAME or DEVICE_GROUP_NAME]/set/digital/outputs/[CHANNEL_NUMBER / OUTPUT_GROUP_NAME]/[PROPERTY]
.
Output channel numbers can be 1 - 16 and the property can only be state. The accepted values that can
be sent to set the output or outputs high are TRUE, HIGH, ON, SET or
1.
The values are not case sensitive.
For example,
jnior/{{ctrl.SerialNumber}}/set/digital/outputs/1/state = true
Where {{ctrl.SerialNumber}}
is the unique serial number for the JNIOR and cannot be changed
in the
JNIOR
jnior/{{ctrl.HostName}}/set/digital/outputs/1/state = true
Where {{ctrl.HostName}}
is the hostname given to the JNIOR. Please note that the
HostName
can be changed in the JNIOR which would affect your system.
jnior/pumpstations/set/digital/outputs/pumps/state = true
pumps
Outputs Group on all
JNIORs belonging to the pumpstations
Device Group. Please note
that the Outputs Group and Device Group can be changed in the JNIOR which would affect
your system.
You can command the JNIOR External 4-20ma Outputs by publishing to the following topic
jnior/[SERIAL_NUMBER or HOSTNAME or DEVICE_GROUP_NAME]/set/fourtwenty/outputs/[CHANNEL_NUMBER]/percentage
.
Output channel numbers can be 1 - 4. The percentage value must be from 0 to 100.
You can command the JNIOR External 0-10v Outputs by publishing to the following topic
jnior/[SERIAL_NUMBER or HOSTNAME or DEVICE_GROUP_NAME]/set/tenvolt/outputs/[CHANNEL_NUMBER]/percentage
.
Output channel numbers can be 1 - 4. The percentage value must be from 0 to 100.